Temperature limits and derating, per platform
What temperature actually stops a Zero, separated into the five different figures Zero publishes for it: the pack operating range the BMS enforces, the charge window inside that range, where charge current starts to taper, the cell manufacturer’s absolute discharge floor, and the storage floor — 352 figures read out of 35 official manuals across 10 thermal regimes from MY2015 to MY2026, each traceable to a document and to a page confirmed in the PDF itself. It cannot tell you your motor or controller thresholds, because outside the Cypher III dash gauges Zero does not publish them and the numbers in circulation come from one bike’s CAN bus.
Your manual is the authority. Every temperature here is transcribed from Zero’s own manuals and each one names the document and page it came from, but a transcription is still a transcription — and these figures differ by platform AND by model year, so a number read off the wrong row is worse than no number. Check anything you plan a cold ride or a hot charge around against the manual for your own model year.
TL;DR
- The single most dangerous figure in circulation is -30 °C as the temperature at which a Zero stops. No platform stops there. On the S / DS / SR / DSR and FX / FXS / FXE platforms of MY2016–2018 the BMS turns the power controller off outside -5 °C (23 °F) to 60 °C (140 °F), and from MY2019 onward outside -20 °C (-4 °F) to 60 °C (140 °F). Against a claimed -30 °C that is 25 °C of margin that does not exist on a MY2016–2018 bike and 10 °C that does not exist on a newer one.
- -30 °C is a real number in Zero’s manuals, which is why the error survived: it is the cell manufacturer’s absolute lowest discharge temperature, and it sits in the winter-storage discussion of chapter 7, not in the operating chapter. Every S / DS / SR / DSR and FX / FXS / FXE manual from MY2015 to MY2018 states it as -30 °C (-22 °F); from MY2019 the same sentence in the same manuals states -20 °C (-4 °F) instead. The Cypher III manuals — SR/F, SR/S, DSR/X and the ADV line — still say -30 °C (-22 °F). So the figure is simultaneously correct in one chapter and wrong in the table that copied it.
- The hot end is stated the opposite way round from how the archive tabulates it. Riding is permitted to 60 °C (140 °F), measured at the pack, and it is CHARGING that stops first: charge current begins to taper above 43 °C (109 °F) and the BMS refuses to charge at all above 50 °C (122 °F). On a hot day the failure you meet is a bike that still rides and will not accept a charge, not a bike that will not move. The archive labels 50–60 °C "operation prevented", which inverts that.
- Ten figures moved between model years, computed by comparing every statement across all 35 documents rather than by reading a changelog. Five moved on each Gen2 platform and all ten landed at the same two boundaries: the charge ceiling fell from 55 °C to 50 °C at MY2016, and at MY2019 the operating floor dropped from -5 °C to -20 °C while the cell floor rose from -30 °C to -20 °C — the two figures crossed each other in the same model year, in the same manual.
- The Cypher III bikes are the only Zeros with a published motor temperature figure, and it is not in a specification table but in the dash gauge legend: the motor gauge turns red at 118 °C (244 °F) and its scale ends at 150 °C (302 °F), identically in all 13 manuals that print it, MY2020 to MY2026. The battery gauge gained a fourth band at MY2022: the white band was cut back from 55 °C to 50 °C and a yellow band inserted above it, putting the boundary exactly where charging stops.
- The motor and controller thresholds the archive tabulates — normal to 100 C, stage 1 to 145 C for the motor, 70 C and 75 C for the controller — appear in no Zero manual in the index. The archive says so itself for the controller: "Pulled from a 2016 Zero SR through CAN bus MBB". The motor table carries no such caveat and has the same origin. They are one owner’s observation of one bike and one firmware, useful for reading that bike’s logs and not a specification for yours.
- Zero also contradicts itself, and the contradiction is live. The current FX/FXS/FXE service manual states the operating range as -5 °C (23 °F) at its low end while every FX owner manual for the same model years — MY2020 to MY2025 — states -20 °C (-4 °F). That is 6 of the 12 document-versus-document conflicts this page computes; the other six are the storage floor in the same two documents. A workshop reading the service manual and an owner reading the owner manual get different answers about the same motorcycle.
- What the archive gets right is worth saying, because a page that only lists errors teaches a reader to distrust everything. Its charge floor of 0 C is correct on every platform in the index — all 34 documents that state a pack charge floor give exactly that. Its taper band of 43–50 °C is correct. Its 60 C upper bound is correct. The structural error is that it puts charge limits and discharge limits in one row of one table, and the two windows are not the same window.
- Every figure here is checked twice: once against the manual it came from, and once against the definition of the unit. Zero prints all 352 of them in both Fahrenheit and Celsius, so C = (F − 32) / 1.8 grades the manufacturer’s own arithmetic — 0 of 352 pairs disagree, which is a cleaner result than the same check gets on Zero’s torque tables.
There is no such thing as "the" temperature limit
A Zero owner manual states at least five different temperatures about the pack, and they live in two chapters that never cross-reference each other. The battery chapter gives the operating range the BMS enforces and the window inside which charging is permitted. The troubleshooting chapter, forty to eighty pages later under "Cold and Hot Weather Considerations", gives a riding advisory, the cell manufacturer’s absolute discharge floor, and a storage floor. All five are real, none of them is "the limit", and picking the wrong one is how a 25 °C error gets into circulation.
The distinction that matters most is enforcement. Two of the five are things the BMS does: it turns the power controller off outside the operating range, and it refuses to charge outside the charge window. Two are advice: do not ride below this, do not store below that. One — the cell floor — is a statement about the chemistry, quoted from the cell supplier, describing the temperature below which discharging damages cells rather than the temperature at which anything stops you.
A figure without its category is unusable, so every row on this page names which of the five it is. The rest of the page is that table, per platform, per model year, with the document and page behind each figure.
| Figure | Enforced by | Chapter | What it is not |
|---|---|---|---|
| Pack operating range | BMS — turns off the power controller outside it | Battery / Power Pack | Not a comfort range. Outside it the bike does not run. |
| Charge window | BMS — refuses to charge outside it | Battery / Power Pack, same paragraph | Not the same as the operating range. It is narrower at both ends. |
| Charge taper onset | The charger — reduces current, charging continues | Troubleshooting, Hot Weather | Not a fault. A slow charge on a hot day is this working. |
| Cell discharge floor | Nothing. It is the cell supplier’s specification | Troubleshooting, Cold Weather | Not where the bike stops. This is the figure the archive misfiled. |
| Storage floor | Nothing. Advice about permanent capacity loss | Troubleshooting, Cold Weather | Not about riding at all, and it moved between model years too. |
Chapter names are Zero’s own headings. The two Battery-chapter figures are one sentence and its note; the three Troubleshooting figures are three sentences of one section. Nothing in either chapter warns the reader that the other exists, which is the structural reason this confusion is so durable.
Every figure on this page is a PACK temperature, not an ambient one
Zero states the discharge cutoff "as measured at the power pack". A pack that has just been ridden hard is well above ambient, and a pack that has sat out overnight lags a warming morning by hours. Ambient temperature appears in only two of these figures — the storage advice, and the direct-sunlight note — and both say ambient explicitly.
The -30 °C error, and why it survived so long
The community archive’s temperature page prints one table, headed "BMS Behavior over Temperature Ranges", whose cold end reads "operation prevented … -22F / -30C" and "charging prevented -22F … 32F (-30C … 0C)". The same table is reproduced on its Main Contactor and Contactor pages, which is why it is the first thing a rider finds when searching for how cold a Zero will run.
The figure is not invented. Every S / DS / SR / DSR and FX / FXS / FXE owner manual from MY2015 through MY2018 contains the sentence "the Battery Management System (BMS) will not allow the battery to be discharged below -30 °C (-22 °F), which is the absolute lowest discharge temperature prescribed by the cell manufacturer" — and it is in the winter-storage discussion, 50 pages after the operating range it was mistaken for.
The operating chapter of those same manuals is far more restrictive. It says the pack "should not be used outside of the range of -5 °C (23 °F) to 60 °C (140 °F); the Battery Management System (BMS) turns off the power controller outside of this range." That is OM-SDS-MY16-English-06.pdf, p63. The two sentences are in the same document, 25 °C apart, and the table copied the wrong one into a column headed "operation prevented".
The figure below draws both. The archive’s claimed cutoff is the dashed line on the left; the band where the platform you select actually rides is the green one. The distance between them is the error, and on the platform that table was built from — a 2016 SR — it is the widest.
| Platform | Model years | BMS operating floor | Cell discharge floor | Manual |
|---|---|---|---|---|
| S / DS / SR / DSR | MY2015 | -5 °C (23 °F) | -30 °C (-22 °F) | OM-SDS-MY15-English.pdf, p56 / p119 |
| S / DS / SR / DSR | MY2016–2018 | -5 °C (23 °F) | -30 °C (-22 °F) | OM-SDS-MY16-English-06.pdf, p63 / p113 |
| S / DS / SR / DSR | MY2019–2023 | -20 °C (-4 °F) | -20 °C (-4 °F) | OM-SDS-MY19-04.pdf, p65 / p115 |
| FX / FXS / FXE | MY2015 | -5 °C (23 °F) | -30 °C (-22 °F) | OM-XMX-MY15-English.pdf, p50 / p119 |
| FX / FXS / FXE | MY2016–2018 | -5 °C (23 °F) | -30 °C (-22 °F) | OM-XMX-MY16-English-04.pdf, p59 / p117 |
| FX / FXS / FXE | MY2019–2025 | -20 °C (-4 °F) | -20 °C (-4 °F) | OM-XMX-MY19-04.pdf, p63 / p125 |
| SR/F & SR/S | MY2020–2026 | -20 °C (-4 °F) | -30 °C (-22 °F) | OM-SRF-MY20.pdf, p97 / p146 |
| DSR/X | MY2023–2025 | -20 °C (-4 °F) | -30 °C (-22 °F) | 23_DSRX_OM_-_English_-_88-09970-AK.pdf, p87 / p148 |
| FST ADV | MY2024–2026 | -20 °C (-4 °F) | -30 °C (-22 °F) | 24MY_FST_ADV_OM_-_English-_EU_-_8811908-AH.pdf, p87 / p148 |
Two pages are given where the two figures are in different chapters, which is every row. The manual named is the earliest in that regime; the figures are identical in every manual of the regime, which is what makes it a regime. Page numbers are PDF pages in the file named, not printed page numbers, and each is looked for in the PDF itself rather than inferred from where the indexed text block began — 360 of the 360 citations on this page are confirmed that way, with none unconfirmed.
Wrong in the community archive: -30 °C is not where the bike stops
The archived table states, under "Cold Battery / operation prevented", the range "… -22F" and "… -30C", implying a Zero runs down to -30 °C and only blocks charging above it. What that figure actually is: the cell manufacturer’s absolute lowest DISCHARGE temperature, quoted in the winter-storage section — OM-SDS-MY16-English-06.pdf, p113 for the platform the table was built from. The measurement that settles it: the operating chapter of the same manual specifies -5 °C (23 °F) to 60 °C (140 °F) and says the BMS turns the power controller off outside it (OM-SDS-MY16-English-06.pdf, p63). What to do instead: plan cold riding against -5 °C on a MY2016–2018 S, SR, DS, DSR, FX or FXS, and against -20 °C on anything from MY2019 onward including every Cypher III bike. If you have been treating -30 °C as the floor, you have been assuming 25 °C of margin that does not exist.
The cell floor and the operating floor crossed each other at MY2019
Between MY2018 and MY2019 the same sentence in the same manuals changed from -30 °C to -20 °C, while the operating floor moved the other way, from -5 °C to -20 °C. From MY2019 on the Gen2 platforms the two figures are the same number, which reads like a simplification and is not one: the Cypher III manuals kept the cell floor at -30 °C while stating the same -20 °C operating floor. Do not infer either figure from the other.
The cold end, in the order you meet it
Riding into falling temperatures, four things happen in sequence, and only the last of them stops you. Reading them in order is more useful than any single figure, because the first three are what you will actually experience.
First, range falls, with no warning and no fault. The manuals put a number on it: compared with operation at 27 °C ambient, at -1 °C ambient "the rider could experience a temporary reduction in range of up to 30%" — OM-SDS-MY15-English.pdf, p119, and the same sentence with the same three figures recurs across the cold-weather sections this page reads. No coverage count is given for it on purpose: the sentence spans a column break in most of these PDFs and the number of documents an automated pass can recover it from says more about the text layer than about the manuals. The loss is temporary — they are explicit that cold operation has "no permanent impact on its power pack/cells".
Second, charging stops before riding does. The BMS will not charge below 0 °C (32 °F), and that figure has never moved: 34 of the 35 documents state a pack charge floor and all 34 give the same 0 °C, a single value across 12 model years. (The thirty-fifth document is the LS1 manual, which states a charging-environment range instead.) That makes it the least ambiguous figure on this page. A bike parked outside below freezing is therefore a bike you can ride and cannot replenish, and the manuals give the remedy: if you do ride it cold, its pack "needs to be put on the charger at a temperature above 0 °C (32 °F) as soon as the ride is concluded".
Third, Zero advises against riding at all below -5 °C (23 °F). This is the most under-quoted figure in the whole set, and the most broadly applicable: 33 of the 35 documents carry it and every one gives the same -5 °C, from MY2015 through every Cypher III manual up to MY2026. It is an advisory rather than a cutoff — the bike will ride below it — and on a MY2016–2018 Gen2 bike it happens to coincide exactly with the BMS operating floor, which is probably why so many readers have concluded that Zero states only one cold figure.
Fourth, the BMS turns the power controller off. That is the operating floor in the table above: -5 °C through MY2018 on the Gen2 platforms, -20 °C from MY2019 and on every Cypher III bike.
There is a fifth cold behaviour that only the Cypher III bikes have, and it is the one most likely to be mistaken for a fault. Those bikes heat their 12 V battery, and while they do it they will not move.
| Platform | Model years | Charging stops below | Riding discouraged below | BMS cutoff | Storage floor |
|---|---|---|---|---|---|
| S / DS / SR / DSR | MY2015 | 0 °C (32 °F) | -5 °C (23 °F) | -5 °C (23 °F) | -35 °C (-31 °F) |
| S / DS / SR / DSR | MY2016–2018 | 0 °C (32 °F) | -5 °C (23 °F) | -5 °C (23 °F) | -35 °C (-31 °F) |
| S / DS / SR / DSR | MY2019–2023 | 0 °C (32 °F) | -5 °C (23 °F) | -20 °C (-4 °F) | -20 °C (-4 °F) |
| FX / FXS / FXE | MY2015 | 0 °C (32 °F) | -5 °C (23 °F) | -5 °C (23 °F) | -35 °C (-31 °F) |
| FX / FXS / FXE | MY2016–2018 | 0 °C (32 °F) | -5 °C (23 °F) | -5 °C (23 °F) | -35 °C (-31 °F) |
| FX / FXS / FXE | MY2019–2025 | 0 °C (32 °F) | -5 °C (23 °F) | -20 °C (-4 °F) | -20 °C (-4 °F) |
| SR/F & SR/S | MY2020–2026 | 0 °C (32 °F) | -5 °C (23 °F) | -20 °C (-4 °F) | -35 °C (-31 °F) |
| DSR/X | MY2023–2025 | 0 °C (32 °F) | -5 °C (23 °F) | -20 °C (-4 °F) | -35 °C (-31 °F) |
| FST ADV | MY2024–2026 | 0 °C (32 °F) | -5 °C (23 °F) | -20 °C (-4 °F) | -35 °C (-31 °F) |
| Light line (LS1 / XB / XE) | MY2026 | -10 °C (14 °F) ambient | — | -20 °C (-4 °F) | — |
The light line is the 2026 LS1 scooter, whose manual states a single operating range and a charging-ENVIRONMENT range rather than a pack charge window, so its charging column is not the same measurement as the others and is marked ambient. Its architecture is a removable pack, not a Zero monolith, and nothing else on this page transfers to it.
A Cypher III bike that refuses to move on a cold morning is probably not broken
The SR/F, SR/S, DSR/X and ADV manuals state that the 12 volt battery "is equipped with a heater to warm it when current (or recent) temperatures have been recorded below 5 °C (41 °F)", and that "during this warming, the motorcycle will be temporarily disabled for 1-15 minutes until the temperature of the 12 volt battery is determined to be above 0 °C (32 °F)". Fifteen minutes of a bike that will not go is normal below 5 °C. This is OM-SRF-MY20.pdf, p146, and it has no equivalent on any Gen2 platform.
The hot end stops charging long before it stops riding
The hot end has the same structure as the cold end and the archive tabulates it backwards, so it is worth stating plainly: on a hot day the first thing you lose is charge rate, the second is charging altogether, and only well beyond that does the bike stop.
Charge current starts to taper above 43 °C (109 °F) — "the charger reduces its charge current to the power pack, increasing charge time accordingly; the hotter the ambient temperature, the greater the effect". Charging is refused outright above 50 °C (122 °F). Riding continues to 60 °C (140 °F), "as measured at the power pack", and that is the figure the BMS enforces by disabling the power controller.
So the realistic hot-weather failure is a bike that carried you to a charger and then will not take a charge until it cools. The archive’s own Overheating page describes exactly this from the rider’s side — slowing for the last few miles before charging to let the pack shed heat — which is sound advice that its temperature table then contradicts by labelling the same band "operation prevented".
One rounding artefact is worth flagging so nobody reads it as a specification change. The taper onset is printed as 43 °C (110 °F) in the Cypher III and MY2015–2018 manuals and as 43 °C (109 °F) from MY2019 on the Gen2 platforms. 109 °F and 110 °F both round to 43 °C, so the Celsius figure never moved and this generator does not report it as a change.
| Platform | Model years | Charge taper from | Charging refused above | Riding blocked above | Sunlight storage limit |
|---|---|---|---|---|---|
| S / DS / SR / DSR | MY2015 | 43 °C (110 °F) | 55 °C (131 °F) | 60 °C (140 °F) | 41 °C (105 °F) ambient |
| S / DS / SR / DSR | MY2016–2018 | 43 °C (110 °F) | 50 °C (122 °F) | 60 °C (140 °F) | 41 °C (105 °F) ambient |
| S / DS / SR / DSR | MY2019–2023 | 43 °C (109 °F) | 50 °C (122 °F) | 60 °C (140 °F) | 35 °C (95 °F) ambient |
| FX / FXS / FXE | MY2015 | 43 °C (110 °F) | 55 °C (131 °F) | 60 °C (140 °F) | 41 °C (105 °F) ambient |
| FX / FXS / FXE | MY2016–2018 | 43 °C (110 °F) | 50 °C (122 °F) | 60 °C (140 °F) | 41 °C (105 °F) ambient |
| FX / FXS / FXE | MY2019–2025 | 43 °C (109 °F) | 50 °C (122 °F) | 60 °C (140 °F) | 35 °C (95 °F) ambient |
| SR/F & SR/S | MY2020–2026 | 43 °C (110 °F) | 50 °C (122 °F) | 60 °C (140 °F) | 41 °C (105 °F) ambient |
| DSR/X | MY2023–2025 | 43 °C (110 °F) | 50 °C (122 °F) | 60 °C (140 °F) | 41 °C (105 °F) ambient |
| FST ADV | MY2024–2026 | 43 °C (110 °F) | 50 °C (122 °F) | 60 °C (140 °F) | 41 °C (105 °F) ambient |
| Light line (LS1 / XB / XE) | MY2026 | — | 50 °C (122 °F) ambient | 55 °C (131 °F) | — |
The sunlight column is the only ambient figure in this table: "Storing the motorcycle or its battery in direct sunlight in ambient temperatures above this may result in accelerated permanent decay of power pack performance." It tightened from 41 °C to 35 °C on the Gen2 platforms at MY2019 while the Cypher III manuals kept 41 °C.
Wrong in the community archive: the 50–60 °C band is not "operation prevented"
The archived table labels 50–60 °C (122F–140F) "operation prevented" and 43–50 °C "charging tapered". What it actually is: charging is refused above 50 °C (122 °F) while riding is permitted all the way to 60 °C (140 °F). The measurement that killed it: the Hot Weather Operation section states both bounds in adjacent sentences — the BMS "will not allow motorcycle operation and its associated power pack discharge above 60 °C (140 °F)" and "Above a power pack temperature of 50 °C (122 °F), the BMS will no longer allow charging" (OM-SDS-MY19-04.pdf, p116). What to do instead: on a hot day expect to lose charging, not propulsion, and do not plan a fast charge straight off a highway run. The archive’s taper band itself is correct.
The charge ceiling was 55 °C on MY2015 bikes
On MY2015 S, DS, SR, DSR and FX the BMS refused charging above 55 °C (131 °F), not 50 °C — and the charging chapter of those manuals tells the owner to "ensure the internal temperature is below 55 °C (131 °F)" when a pack will not accept a charge. From MY2016 the figure is 50 °C on every platform in the index. If you own a MY2015 bike, the 50 °C figure everyone quotes is 5 °C tighter than yours.
What moved between model years, computed rather than asserted
Comparing every temperature statement across all 35 documents finds 10 figures that changed between MY2015 and MY2026. The comparison is done on the Celsius value, so a figure re-typeset or re-rounded without the specification moving does not appear here — which is why the taper onset, printed as two different Fahrenheit numbers, is absent.
Every one of the 10 changes is on a Gen2 platform, 5 on each, and they cluster at two boundaries: MY2016 and MY2019. The Cypher III platforms have not moved a single figure since the SR/F launched for MY2020, which is the strongest thing this dataset says about them: 7 model years and 9 manuals with an identical thermal envelope.
That stability is also why a regime is the right unit here rather than a model year. The 35 documents collapse into 10 regimes; the largest covers 7 model years and the smallest covers one.
| Platform | Figure | Was | Became | Changed at |
|---|---|---|---|---|
| FX / FXS / FXE | charge high | 55 °C (MY2015) | 50 °C (MY2016) | MY2016 |
| FX / FXS / FXE | operating low | -5 °C (MY2018) | -20 °C (MY2019) | MY2019 |
| FX / FXS / FXE | cell discharge floor | -30 °C (MY2018) | -20 °C (MY2019) | MY2019 |
| FX / FXS / FXE | storage floor | -35 °C (MY2018) | -20 °C (MY2019) | MY2019 |
| FX / FXS / FXE | sun storage ceiling | 41 °C (MY2018) | 35 °C (MY2019) | MY2019 |
| S / DS / SR / DSR | charge high | 55 °C (MY2015) | 50 °C (MY2016) | MY2016 |
| S / DS / SR / DSR | operating low | -5 °C (MY2018) | -20 °C (MY2019) | MY2019 |
| S / DS / SR / DSR | cell discharge floor | -30 °C (MY2018) | -20 °C (MY2019) | MY2019 |
| S / DS / SR / DSR | storage floor | -35 °C (MY2018) | -20 °C (MY2019) | MY2019 |
| S / DS / SR / DSR | sun storage ceiling | 41 °C (MY2018) | 35 °C (MY2019) | MY2019 |
"Changed at" is the first model year in the index carrying the new figure. If a manual for an intervening year is missing from the index the change may have landed earlier. Rows where only the printed Fahrenheit figure or its rounding moved are excluded by design.
The Cypher III dash gauges, and the only published motor figure
The Cypher III bikes replaced the Gen2 warning lamp with two graphical gauges — pack and motor — whose bars change colour with temperature. The manual prints the colour boundaries as a table, and notes that "the battery and motor temperature gauges do not have a numerical value display function", so those boundaries are the only numbers the rider ever sees.
That table is also the only place in 35 indexed documents where Zero publishes a motor temperature threshold: the motor gauge is white from 20 °C (68 °F) to 118 °C (244 °F) and red from there to 150 °C (302 °F), identically in all 13 manuals that print it. Nothing states what happens at 150 °C; it is where the scale ends, not a documented cutoff.
The battery gauge changed at MY2022. Through MY2021 it had three bands, with white running to 55 °C. From MY2022 it has four: white was cut back to 50 °C and a yellow band inserted from there to 55 °C. The new boundary is exactly the temperature above which the BMS refuses to charge (50 °C), so from MY2022 the gauge tells you when you have lost charging. Before that, it did not.
Two things about these bands are worth noticing because they are easy to over-read. The blue band starts at -10 °C, which is 10 °C above the BMS operating floor of -20 °C — the gauge simply has no band for the coldest 10 °C in which the bike still runs. And the red band ends at 75 °C, 15 °C above the 60 °C at which riding is blocked. Neither end of the gauge is a limit; both are just the end of the drawing.
| Gauge | Model years | Bands (°C) | Bands (°F) | Manuals |
|---|---|---|---|---|
| Battery temperature | MY2020–2021 | blue -10 to 10 · white 10 to 55 · red 55 to 75 | 14 to 50 · 50 to 131 · 131 to 167 | 4 |
| Battery temperature | MY2022–2026 | blue -10 to 10 · white 10 to 50 · yellow 50 to 55 · red 55 to 75 | 14 to 50 · 50 to 122 · 122 to 131 · 131 to 167 | 9 |
| Motor temperature | MY2020–2026 | white 20 to 118 · red 118 to 150 | 68 to 244 · 244 to 302 | 13 |
Read straight from the "Color / Motor Temperature Range" and "Color / Battery Temperature Range" tables in the General Operation chapter. Both Fahrenheit and Celsius columns are Zero’s own; every pair passes the unit check. The colour names are Zero’s and describe the gauge bars, not a severity scale.
The Gen2 dash shows motor temperature as a number
All 22 Gen2 owner manuals in the index (MY2014–MY2025) describe a dash readout: "Temp - Displays the temperature of the motor in Fahrenheit (F) or Celsius (C)", with the caveat that "the temperature may not read accurately during the first 5 miles of a ride". That readout is where community motor-temperature figures come from. It is a measurement of your motor, which is useful; it is not a published threshold, which is what people have used it as.
What derating actually does, and what the lamp means
Zero’s powertrain is passively air-cooled, and the manuals are unusually candid about the consequence: it "cannot be operated indefinitely at high power / high rpm without reaching its thermal limitations", so there is a "thermal management strategy" that reduces power rather than letting the hardware cook. What the rider sees differs by generation, and the vocabulary the community uses comes from the Gen2 version of it.
On the Gen2 platforms the temperature lamp is yellow and has two stages, in Zero’s own words. Stage 1 is the lamp flashing, which "advises you that the bike is about to enter its thermal strategy" — performance is not yet affected and slowing down a little will clear it. Stage 2 is the lamp solid, meaning the strategy is being applied and power is being reduced. This wording appears in all 22 Gen2 owner manuals in the index, MY2014–MY2025, unchanged.
On the Cypher III platforms there are no stages. The manuals describe a single red lamp that "illuminates when the motorcycle’s powertrain enters its thermal strategy", solid, with power already reduced — the warning stage was replaced by the two gauges, which let the rider watch the temperature rise instead of being told once that it is about to matter.
What derating feels like is also documented, and it is not what most riders expect. Held at speed, the bike "will be gradually slowed down to the point that the top speed of the bike is sustainable, from a thermal standpoint" — you lose top speed, not throttle response. In a different sustained-load case, such as "continued powering through a low traction surface", power is simply reduced. The manuals state twice that this is not a fault: "no harm whatsoever will result from this, since this is exactly how the strategy is meant to function."
None of that text carries a temperature. Zero documents the behaviour and the lamp and publishes no threshold at which either begins, on any platform, in any of the 35 documents indexed here. That absence is the reason the next section exists.
A flashing lamp is the only free warning you get
On a Gen2 bike, Stage 1 costs you nothing and is the cue to ease off before the bike decides for you. On a Cypher III bike there is no Stage 1: by the time the red lamp is on, power is already reduced, and the gauges are the early warning instead. If you ride a Cypher III hard, watch the motor gauge rather than waiting for a light.
The motor and controller numbers, and where they really come from
The archive publishes two more tables in the same Quick Reference style as the battery one: a motor table with Normal to 100 C, Stage 1 from 100 C to 145 C and Stage 2 above 145 C, and a controller table with Normal to 70 C, Stage 1 from 70 C to 75 C and Stage 2 above 75 C. They look exactly as authoritative as the battery table, and they use Zero’s own Stage 1 / Stage 2 vocabulary, which makes them read like specifications.
The controller page says where they come from, in a single line above the table: "Pulled from a 2016 Zero SR through CAN bus MBB / other years, firmware revisions, and dash temperature lights may be different." That is an honest provenance statement and it should be read as covering the motor table too, which sits immediately above it, carries no caveat, and has the same origin. One bike, one firmware, one afternoon.
The reason those tables read as specifications is that their STRUCTURE is Zero’s own. The dash error-code table in all 22 Gen2 owner manuals lists four named thermal warnings — code 2 "Motor Temperature Warning Stage 1", code 3 "Motor Temperature Warning Stage 2", code 4 "Controller Temperature Warning Stage 1", code 5 "Controller Temperature Warning Stage 2" — and gives no temperature for any of them. So Stage 1 and Stage 2 are real, documented states of a real dash. What the archive added was the temperatures, from one bike, and the two things now travel together as though they had the same provenance.
The Cypher III manuals name their thermal warnings differently and are just as silent about temperature: in 12 of them the error table gives code 55 "Battery Temperature High" and code 56 "Battery Temperature Low", both with the consequence "Performance will be reduced and Charging may be disabled", and code 57 "Controller High Temperature — Performance will be reduced". There is no motor code at all on that platform, and no stages: the two gauges replaced them.
Searched against the index, no Zero manual attaches a temperature to any of those seven named warnings, and the only motor figures anywhere are the Cypher III gauge bands in the previous section — 118 °C and 150 °C, for a different platform with a different motor. The archive’s 100 C and 145 C are neither confirmed nor refuted by anything Zero publishes; they are simply unpublished, and the honest thing to do with them is to keep them labelled as one bike’s CAN bus rather than delete them.
That labelling matters more than it sounds, because these numbers are not useless. A Gen2 rider reading their own logs and seeing motor temperature climb past 100 C now knows that at least one bike’s dash lit its lamp around there. What they must not do is conclude that 145 C is a limit their firmware enforces, or that 100 C is abnormal — the archive’s own Overheating page notes that on 2014-and-later SR and DSR motors "it is normal to see 120+C under spirited riding".
| Figure | Value | Source | Status |
|---|---|---|---|
| Motor gauge white→red boundary, Cypher III | 118 °C (244 °F) | 13 owner manuals, MY2020–2026 | Published by Zero |
| Motor gauge scale end, Cypher III | 150 °C (302 °F) | 13 owner manuals, MY2020–2026 | Published, but it is the end of a gauge, not a stated cutoff |
| Motor Stage 1 onset, Gen2 | 100 °C | Community archive, one 2016 SR read over CAN | Unconfirmed. No manual states it |
| Motor Stage 2 onset, Gen2 | 145 °C | Community archive, one 2016 SR read over CAN | Unconfirmed. No manual states it |
| Controller Stage 1 onset, Gen2 | 70 °C | Community archive, explicitly one 2016 SR over CAN | Unconfirmed. No manual states any controller threshold |
| Controller Stage 2 onset, Gen2 | 75 °C | Community archive, explicitly one 2016 SR over CAN | Unconfirmed. No manual states any controller threshold |
| Motor / Controller Temperature Warning, Stage 1 and Stage 2 | No temperature given | 22 Gen2 owner manuals, error-code table, codes 2–5 | Zero names the four stages and publishes no threshold for any of them |
| Battery Temperature High / Low, Controller High Temperature | No temperature given | 12 Cypher III owner manuals, error-code table, codes 55–57 | Named, with the consequence stated and no threshold |
| Motor temperature dash readout, Gen2 | Numeric, °F or °C | 22 Gen2 owner manuals, Instrument Cluster chapter | Published as a readout, with a first-5-miles accuracy caveat |
The four unconfirmed rows are reproduced with their provenance rather than dropped, because a rider who has already read them needs to recognise them. A figure measured on one bike is evidence about that bike; it becomes a specification only when the manufacturer states it, and here the manufacturer does not.
Retracted: our own earlier note said no manual publishes a motor threshold
An earlier verification pass on this corpus recorded that "no motor or controller temperature threshold appears anywhere in the 46 manuals". That is right for the controller and wrong for the motor: the Cypher III dash gauge table gives 118 °C and 150 °C, in 13 manuals, MY2020 to MY2026. It was missed because it is typeset as a gauge legend in the General Operation chapter rather than as a specification, which is exactly the kind of place a keyword search for "temperature limit" does not look. The figures are now generated from that table, so the omission cannot recur silently.
Our own analyzer thresholds are not OEM figures either
This site’s log health scoring flags a motor temperature above 130 °C and a pack temperature above 55 °C. Neither is a published Zero limit: 130 °C sits between the Cypher III gauge’s 118 °C red boundary and its 150 °C scale end and matches nothing on a Gen2 bike, and 55 °C is 5 °C below the 60 °C at which Zero actually blocks discharge. They are heuristics for drawing your attention to an outlier, they are being reconciled against the figures on this page, and they should never be quoted as limits.
Where Zero contradicts Zero
Intersecting the model years of every pair of documents that cover one platform finds 12 places where two Zero publications state different values for the same figure about the same motorcycle. All of them involve one document, and it is a current one.
The FX / FXS / FXE service manual (XMX_Service_Manual_8811943-AF.pdf) covers MY2020 to MY2025 and reproduces the pre-MY2019 cold-weather text: on its p56 it gives the operating range low end as -5 °C (23 °F), and on p57 the storage floor as -35 °C (-31 °F). The FX owner manuals for those same model years give -20 °C (-4 °F) and -20 °C (-4 °F). Six years of motorcycles are documented twice, differently, by their own manufacturer.
Which one to believe is not a coin toss. The owner manual is model-year specific and the figures in it moved in step with the rest of that year’s thermal set, while the service manual is a multi-year document that appears to have carried the older chapter forward — the same failure mode as the community torque page. On this one, prefer the owner manual for your model year, and treat the service manual’s -5 °C (23 °F) as the conservative reading rather than the correct one: it is more restrictive, so following it costs you cold-weather range and nothing else.
| Platform | Figure | Model years | Document A | Document B |
|---|---|---|---|---|
| FX / FXS / FXE | operating low | MY2020 | -20 °C — OM-XMX-MY20-English-04.pdf p61 | -5 °C — XMX_Service_Manual_8811943-AF.pdf p56 |
| FX / FXS / FXE | operating low | MY2021 | -5 °C — XMX_Service_Manual_8811943-AF.pdf p56 | -20 °C — 21MY_XMX_OM_-_English-05.pdf p61 |
| FX / FXS / FXE | operating low | MY2022 | -5 °C — XMX_Service_Manual_8811943-AF.pdf p56 | -20 °C — 22MY_XMX_OM_-_English-05.pdf p61 |
| FX / FXS / FXE | operating low | MY2023 | -5 °C — XMX_Service_Manual_8811943-AF.pdf p56 | -20 °C — 23_XMX_OM_-_English-88-09949-AI.pdf p63 |
| FX / FXS / FXE | operating low | MY2024 | -5 °C — XMX_Service_Manual_8811943-AF.pdf p56 | -20 °C — 24_XMX_English_-EU_-_8811914-_AG.pdf p63 |
| FX / FXS / FXE | operating low | MY2025 | -5 °C — XMX_Service_Manual_8811943-AF.pdf p56 | -20 °C — 25_XMX_OM_-_EU_English_-_8811991-AE.pdf p63 |
| FX / FXS / FXE | storage floor | MY2020 | -20 °C — OM-XMX-MY20-English-04.pdf p123 | -35 °C — XMX_Service_Manual_8811943-AF.pdf p57 |
| FX / FXS / FXE | storage floor | MY2021 | -35 °C — XMX_Service_Manual_8811943-AF.pdf p57 | -20 °C — 21MY_XMX_OM_-_English-05.pdf p121 |
| FX / FXS / FXE | storage floor | MY2022 | -35 °C — XMX_Service_Manual_8811943-AF.pdf p57 | -20 °C — 22MY_XMX_OM_-_English-05.pdf p125 |
| FX / FXS / FXE | storage floor | MY2023 | -35 °C — XMX_Service_Manual_8811943-AF.pdf p57 | -20 °C — 23_XMX_OM_-_English-88-09949-AI.pdf p127 |
| FX / FXS / FXE | storage floor | MY2024 | -35 °C — XMX_Service_Manual_8811943-AF.pdf p57 | -20 °C — 24_XMX_English_-EU_-_8811914-_AG.pdf p127 |
| FX / FXS / FXE | storage floor | MY2025 | -35 °C — XMX_Service_Manual_8811943-AF.pdf p57 | -20 °C — 25_XMX_OM_-_EU_English_-_8811991-AE.pdf p127 |
One row per model year, because the owner manual differs per year while the service manual does not. The pairing is by platform and overlapping year list only — no judgement about which document wins is encoded in the data.
Zero’s thermal arithmetic is clean, unlike its torque tables
All 352 figures on this page are printed by Zero in both Fahrenheit and Celsius, which makes every one of them checkable against C = (F − 32) / 1.8. 0 fail. The same check on Zero’s Component Fasteners tables finds a row that has been wrong across five model years, so this is a real difference in quality between two parts of the same manuals rather than a slack tolerance.
Finding these limits in your own logs
Every figure above is about pack temperature, and pack temperature is one of the few fields every Zero generation records. A log tells you which of these limits you have actually met, which is more useful than knowing where they are.
The Gen2 MBB condition record carries a pack high and a pack low temperature, a motor temperature, a controller temperature and an ambient temperature, all in one line, so a cold-weather ride shows up directly as a pack-temperature trace you can lay against the tables above. The Gen3 ring-buffer records carry pack temperatures too, but the buffer holds only a few days on a parked bike, so a thermal event more than a week old has usually been overwritten before the log is pulled.
Two readings are worth checking against this page rather than against intuition. A charge session that stops short and resumes later is often the 50 °C ceiling or the taper, not a charger fault — compare the pack temperature at the moment it stopped. And a winter ride with unusually high energy consumption per kilometre is the cold-range effect the manuals quantify, not degradation; the pack has not lost capacity, it has temporarily lost the ability to release it.
One caution about reading temperature out of a log at all: a value is only as good as the sensor and the decode behind it. Impossible readings do occur, so this project’s parser discards a Gen2 condition record whose pack temperature exceeds 100 °C, whose ambient falls outside −50 °C to 70 °C, whose motor exceeds 200 °C or whose controller exceeds 150 °C — a misaligned record produces plausible-looking garbage rather than obvious nonsense. Those gates are deliberately far outside the figures on this page; the motor gate alone sits 50 °C above the end of the Cypher III motor gauge. If one sample says your pack hit 90 °C and every neighbouring sample says 25 °C, believe the neighbours.
What this page cannot tell you
The scope is the temperature statements in Zero’s own manuals for model years 2015 and later. Five things sit outside it, and each is a real limit on how far these figures can be pushed.
- Model years 2013 and 2014. Their manuals are in the index and their figures differ — the MY2014 charge ceiling is one of them — but those machines are twelve years old and their paper manual should be the only authority on them.
- Motor and controller thresholds on Gen2. Not published, not measurable from the manuals, and the numbers in circulation are one bike’s CAN bus. If you need yours, the dash readout on your own bike is better evidence than any table.
- What the BMS actually does at the boundary, as opposed to that it acts. The manuals say the power controller is turned off; they do not say whether that is abrupt or ramped, whether regen is affected differently from drive, or how much hysteresis there is before it comes back.
- Cell-level temperatures. Every figure here is a pack figure, and a pack has a hot end and a cold end at the same moment — the logs report both — so a pack reported at 45 °C may contain cells meaningfully hotter.
- The 2026 light line beyond its two stated ranges. The LS1 manual gives an operating range of -20 °C (-4 °F) to 55 °C (131 °F) and a charging-environment range of -10 °C (14 °F) to 50 °C (122 °F), and nothing else that maps onto the five figures on this page. Different architecture, removable pack, different document.
A pack outside these ranges is not something to open
Nothing on this page authorises work on the high-voltage system, and a pack that has been overheated or deeply cold-cycled is exactly the case where people are tempted to investigate. A Zero pack sits above 100 V and its terminals stay live with the bike off. If a thermal event has left the bike inoperable, that is a dealer conversation, not a garage one.
Every figure, every manual
All 352 temperature figures, grouped by the manual they were read from and rendered into the page itself so every one is readable with JavaScript off, by a screen reader and by a crawler. Both units are Zero’s own — the Fahrenheit column is what the manual prints, not a conversion of the Celsius one. The PDF page is looked for in the PDF itself rather than taken from where the indexed text block began: 360 of 360 citations are confirmed that way, and none is unconfirmed.
DSR/X — MY2023
23_DSRX_OM_-_English_-_88-09970-AK.pdf · DSR/X
| Figure | °C | °F | PDF page | What it governs |
|---|---|---|---|---|
| operating low | -20 | -4 | p87 | Pack operating range, low end — BMS turns off the power controller below |
| operating high | 60 | 140 | p87 | Pack operating range, high end — BMS turns off the power controller above |
| charge low | 0 | 32 | p87 | Charging inhibited below |
| charge high | 50 | 122 | p149 | Charging inhibited above |
| charge taper | 43 | 110 | p149 | Charge current begins to taper above |
| discharge high cutoff | 60 | 140 | p149 | Discharge (riding) blocked above |
| ride advisory low | -5 | 23 | p148 | Riding not recommended below (advisory, not a BMS cutoff) |
| cell discharge floor | -30 | -22 | p148 | Cell manufacturer's absolute lowest discharge temperature |
| storage floor | -35 | -31 | p148 | Storage below this may permanently decay the pack |
| sun storage ceiling | 41 | 105 | p149 | Storing in direct sunlight above this is not recommended |
| hv12 heater on | 5 | 41 | p148 | 12 V battery heater engages below (Cypher III only) |
DSR/X — MY2025
25_DSRX_EU-English-_8811972-AF.pdf · DS, DSR, DSR/X
| Figure | °C | °F | PDF page | What it governs |
|---|---|---|---|---|
| operating low | -20 | -4 | p87 | Pack operating range, low end — BMS turns off the power controller below |
| operating high | 60 | 140 | p87 | Pack operating range, high end — BMS turns off the power controller above |
| charge low | 0 | 32 | p87 | Charging inhibited below |
| charge high | 50 | 122 | p149 | Charging inhibited above |
| charge taper | 43 | 110 | p149 | Charge current begins to taper above |
| discharge high cutoff | 60 | 140 | p149 | Discharge (riding) blocked above |
| ride advisory low | -5 | 23 | p148 | Riding not recommended below (advisory, not a BMS cutoff) |
| cell discharge floor | -30 | -22 | p148 | Cell manufacturer's absolute lowest discharge temperature |
| storage floor | -35 | -31 | p148 | Storage below this may permanently decay the pack |
| sun storage ceiling | 41 | 105 | p149 | Storing in direct sunlight above this is not recommended |
| hv12 heater on | 5 | 41 | p148 | 12 V battery heater engages below (Cypher III only) |
FST ADV — MY2024
24MY_FST_ADV_OM_-_English-_EU_-_8811908-AH.pdf · DS, DSR, DSR/X
| Figure | °C | °F | PDF page | What it governs |
|---|---|---|---|---|
| operating low | -20 | -4 | p87 | Pack operating range, low end — BMS turns off the power controller below |
| operating high | 60 | 140 | p87 | Pack operating range, high end — BMS turns off the power controller above |
| charge low | 0 | 32 | p87 | Charging inhibited below |
| charge high | 50 | 122 | p149 | Charging inhibited above |
| charge taper | 43 | 110 | p149 | Charge current begins to taper above |
| discharge high cutoff | 60 | 140 | p149 | Discharge (riding) blocked above |
| ride advisory low | -5 | 23 | p148 | Riding not recommended below (advisory, not a BMS cutoff) |
| cell discharge floor | -30 | -22 | p148 | Cell manufacturer's absolute lowest discharge temperature |
| storage floor | -35 | -31 | p148 | Storage below this may permanently decay the pack |
| sun storage ceiling | 41 | 105 | p149 | Storing in direct sunlight above this is not recommended |
| hv12 heater on | 5 | 41 | p148 | 12 V battery heater engages below (Cypher III only) |
FST ADV — MY2026
26_FST_ADV_-_EU_-_English-_8812128-AC.pdf · DS, DSR/X
| Figure | °C | °F | PDF page | What it governs |
|---|---|---|---|---|
| operating low | -20 | -4 | p87 | Pack operating range, low end — BMS turns off the power controller below |
| operating high | 60 | 140 | p87 | Pack operating range, high end — BMS turns off the power controller above |
| charge low | 0 | 32 | p87 | Charging inhibited below |
| charge high | 50 | 122 | p149 | Charging inhibited above |
| charge taper | 43 | 110 | p149 | Charge current begins to taper above |
| discharge high cutoff | 60 | 140 | p149 | Discharge (riding) blocked above |
| ride advisory low | -5 | 23 | p148 | Riding not recommended below (advisory, not a BMS cutoff) |
| cell discharge floor | -30 | -22 | p148 | Cell manufacturer's absolute lowest discharge temperature |
| storage floor | -35 | -31 | p148 | Storage below this may permanently decay the pack |
| sun storage ceiling | 41 | 105 | p149 | Storing in direct sunlight above this is not recommended |
| hv12 heater on | 5 | 41 | p148 | 12 V battery heater engages below (Cypher III only) |
FX / FXS / FXE — MY2015
OM-XMX-MY15-English.pdf · FX
| Figure | °C | °F | PDF page | What it governs |
|---|---|---|---|---|
| operating low | -5 | 23 | p50 | Pack operating range, low end — BMS turns off the power controller below |
| operating high | 60 | 140 | p50 | Pack operating range, high end — BMS turns off the power controller above |
| charge low | 0 | 32 | p50 | Charging inhibited below |
| charge high | 55 | 131 | p120 | Charging inhibited above |
| charge taper | 43 | 110 | p120 | Charge current begins to taper above |
| discharge high cutoff | 60 | 140 | p120 | Discharge (riding) blocked above |
| ride advisory low | -5 | 23 | p119 | Riding not recommended below (advisory, not a BMS cutoff) |
| cell discharge floor | -30 | -22 | p119 | Cell manufacturer's absolute lowest discharge temperature |
| storage floor | -35 | -31 | p119 | Storage below this may permanently decay the pack |
| sun storage ceiling | 41 | 105 | p120 | Storing in direct sunlight above this is not recommended |
FX / FXS / FXE — MY2016
OM-XMX-MY16-English-04.pdf · FX, FXS
| Figure | °C | °F | PDF page | What it governs |
|---|---|---|---|---|
| operating low | -5 | 23 | p59 | Pack operating range, low end — BMS turns off the power controller below |
| operating high | 60 | 140 | p59 | Pack operating range, high end — BMS turns off the power controller above |
| charge low | 0 | 32 | p59 | Charging inhibited below |
| charge high | 50 | 122 | p118 | Charging inhibited above |
| charge taper | 43 | 110 | p118 | Charge current begins to taper above |
| discharge high cutoff | 60 | 140 | p118 | Discharge (riding) blocked above |
| ride advisory low | -5 | 23 | p117 | Riding not recommended below (advisory, not a BMS cutoff) |
| cell discharge floor | -30 | -22 | p117 | Cell manufacturer's absolute lowest discharge temperature |
| storage floor | -35 | -31 | p117 | Storage below this may permanently decay the pack |
| sun storage ceiling | 41 | 105 | p118 | Storing in direct sunlight above this is not recommended |
FX / FXS / FXE — MY2017
OM-XMX-MY17-English-AE.pdf · FX, FXS
| Figure | °C | °F | PDF page | What it governs |
|---|---|---|---|---|
| operating low | -5 | 23 | p59 | Pack operating range, low end — BMS turns off the power controller below |
| operating high | 60 | 140 | p59 | Pack operating range, high end — BMS turns off the power controller above |
| charge low | 0 | 32 | p59 | Charging inhibited below |
| charge high | 50 | 122 | p122 | Charging inhibited above |
| charge taper | 43 | 110 | p122 | Charge current begins to taper above |
| discharge high cutoff | 60 | 140 | p122 | Discharge (riding) blocked above |
| ride advisory low | -5 | 23 | p121 | Riding not recommended below (advisory, not a BMS cutoff) |
| cell discharge floor | -30 | -22 | p121 | Cell manufacturer's absolute lowest discharge temperature |
| storage floor | -35 | -31 | p121 | Storage below this may permanently decay the pack |
| sun storage ceiling | 41 | 105 | p122 | Storing in direct sunlight above this is not recommended |
FX / FXS / FXE — MY2018
OM-XMX-MY18-English-AE.pdf · FX, FXS
| Figure | °C | °F | PDF page | What it governs |
|---|---|---|---|---|
| operating low | -5 | 23 | p61 | Pack operating range, low end — BMS turns off the power controller below |
| operating high | 60 | 140 | p61 | Pack operating range, high end — BMS turns off the power controller above |
| charge low | 0 | 32 | p61 | Charging inhibited below |
| charge high | 50 | 122 | p124 | Charging inhibited above |
| charge taper | 43 | 110 | p124 | Charge current begins to taper above |
| discharge high cutoff | 60 | 140 | p124 | Discharge (riding) blocked above |
| ride advisory low | -5 | 23 | p123 | Riding not recommended below (advisory, not a BMS cutoff) |
| cell discharge floor | -30 | -22 | p123 | Cell manufacturer's absolute lowest discharge temperature |
| storage floor | -35 | -31 | p123 | Storage below this may permanently decay the pack |
| sun storage ceiling | 41 | 105 | p124 | Storing in direct sunlight above this is not recommended |
FX / FXS / FXE — MY2019
OM-XMX-MY19-04.pdf · FX, FXS
| Figure | °C | °F | PDF page | What it governs |
|---|---|---|---|---|
| operating low | -20 | -4 | p63 | Pack operating range, low end — BMS turns off the power controller below |
| operating high | 60 | 140 | p63 | Pack operating range, high end — BMS turns off the power controller above |
| charge low | 0 | 32 | p63 | Charging inhibited below |
| charge high | 50 | 122 | p126 | Charging inhibited above |
| charge taper | 43 | 109 | p126 | Charge current begins to taper above |
| discharge high cutoff | 60 | 140 | p126 | Discharge (riding) blocked above |
| ride advisory low | -5 | 23 | p125 | Riding not recommended below (advisory, not a BMS cutoff) |
| cell discharge floor | -20 | -4 | p125 | Cell manufacturer's absolute lowest discharge temperature |
| storage floor | -20 | -4 | p125 | Storage below this may permanently decay the pack |
| sun storage ceiling | 35 | 95 | p126 | Storing in direct sunlight above this is not recommended |
FX / FXS / FXE — MY2020
OM-XMX-MY20-English-04.pdf · FX, FXS
| Figure | °C | °F | PDF page | What it governs |
|---|---|---|---|---|
| operating low | -20 | -4 | p61 | Pack operating range, low end — BMS turns off the power controller below |
| operating high | 60 | 140 | p61 | Pack operating range, high end — BMS turns off the power controller above |
| charge low | 0 | 32 | p61 | Charging inhibited below |
| charge high | 50 | 122 | p124 | Charging inhibited above |
| charge taper | 43 | 109 | p124 | Charge current begins to taper above |
| discharge high cutoff | 60 | 140 | p124 | Discharge (riding) blocked above |
| ride advisory low | -5 | 23 | p123 | Riding not recommended below (advisory, not a BMS cutoff) |
| cell discharge floor | -20 | -4 | p123 | Cell manufacturer's absolute lowest discharge temperature |
| storage floor | -20 | -4 | p123 | Storage below this may permanently decay the pack |
| sun storage ceiling | 35 | 95 | p124 | Storing in direct sunlight above this is not recommended |
FX / FXS / FXE — MY2020, 2021, 2022, 2023, 2024, 2025 (service manual)
XMX_Service_Manual_8811943-AF.pdf · FX, FXE, FXS
| Figure | °C | °F | PDF page | What it governs |
|---|---|---|---|---|
| operating low | -5 | 23 | p56 | Pack operating range, low end — BMS turns off the power controller below |
| operating high | 60 | 140 | p56 | Pack operating range, high end — BMS turns off the power controller above |
| charge low | 0 | 32 | p56 | Charging inhibited below |
| charge taper | 43 | 110 | p57 | Charge current begins to taper above |
| storage floor | -35 | -31 | p57 | Storage below this may permanently decay the pack |
FX / FXS / FXE — MY2021
21MY_XMX_OM_-_English-05.pdf · FX, FXS
| Figure | °C | °F | PDF page | What it governs |
|---|---|---|---|---|
| operating low | -20 | -4 | p61 | Pack operating range, low end — BMS turns off the power controller below |
| operating high | 60 | 140 | p61 | Pack operating range, high end — BMS turns off the power controller above |
| charge low | 0 | 32 | p61 | Charging inhibited below |
| charge high | 50 | 122 | p122 | Charging inhibited above |
| charge taper | 43 | 109 | p122 | Charge current begins to taper above |
| discharge high cutoff | 60 | 140 | p122 | Discharge (riding) blocked above |
| ride advisory low | -5 | 23 | p121 | Riding not recommended below (advisory, not a BMS cutoff) |
| cell discharge floor | -20 | -4 | p121 | Cell manufacturer's absolute lowest discharge temperature |
| storage floor | -20 | -4 | p121 | Storage below this may permanently decay the pack |
| sun storage ceiling | 35 | 95 | p122 | Storing in direct sunlight above this is not recommended |
FX / FXS / FXE — MY2022
22MY_XMX_OM_-_English-05.pdf · FX, FXE
| Figure | °C | °F | PDF page | What it governs |
|---|---|---|---|---|
| operating low | -20 | -4 | p61 | Pack operating range, low end — BMS turns off the power controller below |
| operating high | 60 | 140 | p61 | Pack operating range, high end — BMS turns off the power controller above |
| charge low | 0 | 32 | p61 | Charging inhibited below |
| charge high | 50 | 122 | p126 | Charging inhibited above |
| charge taper | 43 | 109 | p126 | Charge current begins to taper above |
| discharge high cutoff | 60 | 140 | p126 | Discharge (riding) blocked above |
| ride advisory low | -5 | 23 | p125 | Riding not recommended below (advisory, not a BMS cutoff) |
| cell discharge floor | -20 | -4 | p125 | Cell manufacturer's absolute lowest discharge temperature |
| storage floor | -20 | -4 | p125 | Storage below this may permanently decay the pack |
| sun storage ceiling | 35 | 95 | p126 | Storing in direct sunlight above this is not recommended |
FX / FXS / FXE — MY2023
23_XMX_OM_-_English-88-09949-AI.pdf · FX, FXE
| Figure | °C | °F | PDF page | What it governs |
|---|---|---|---|---|
| operating low | -20 | -4 | p63 | Pack operating range, low end — BMS turns off the power controller below |
| operating high | 60 | 140 | p63 | Pack operating range, high end — BMS turns off the power controller above |
| charge low | 0 | 32 | p63 | Charging inhibited below |
| charge high | 50 | 122 | p128 | Charging inhibited above |
| charge taper | 43 | 109 | p128 | Charge current begins to taper above |
| discharge high cutoff | 60 | 140 | p128 | Discharge (riding) blocked above |
| ride advisory low | -5 | 23 | p127 | Riding not recommended below (advisory, not a BMS cutoff) |
| cell discharge floor | -20 | -4 | p127 | Cell manufacturer's absolute lowest discharge temperature |
| storage floor | -20 | -4 | p127 | Storage below this may permanently decay the pack |
| sun storage ceiling | 35 | 95 | p128 | Storing in direct sunlight above this is not recommended |
FX / FXS / FXE — MY2024
24_XMX_English_-EU_-_8811914-_AG.pdf · FX, FXE
| Figure | °C | °F | PDF page | What it governs |
|---|---|---|---|---|
| operating low | -20 | -4 | p63 | Pack operating range, low end — BMS turns off the power controller below |
| operating high | 60 | 140 | p63 | Pack operating range, high end — BMS turns off the power controller above |
| charge low | 0 | 32 | p63 | Charging inhibited below |
| charge high | 50 | 122 | p128 | Charging inhibited above |
| charge taper | 43 | 109 | p128 | Charge current begins to taper above |
| discharge high cutoff | 60 | 140 | p128 | Discharge (riding) blocked above |
| ride advisory low | -5 | 23 | p127 | Riding not recommended below (advisory, not a BMS cutoff) |
| cell discharge floor | -20 | -4 | p127 | Cell manufacturer's absolute lowest discharge temperature |
| storage floor | -20 | -4 | p127 | Storage below this may permanently decay the pack |
| sun storage ceiling | 35 | 95 | p128 | Storing in direct sunlight above this is not recommended |
FX / FXS / FXE — MY2025
25_XMX_OM_-_EU_English_-_8811991-AE.pdf · FX, FXE
| Figure | °C | °F | PDF page | What it governs |
|---|---|---|---|---|
| operating low | -20 | -4 | p63 | Pack operating range, low end — BMS turns off the power controller below |
| operating high | 60 | 140 | p63 | Pack operating range, high end — BMS turns off the power controller above |
| charge low | 0 | 32 | p63 | Charging inhibited below |
| charge high | 50 | 122 | p128 | Charging inhibited above |
| charge taper | 43 | 109 | p128 | Charge current begins to taper above |
| discharge high cutoff | 60 | 140 | p128 | Discharge (riding) blocked above |
| ride advisory low | -5 | 23 | p127 | Riding not recommended below (advisory, not a BMS cutoff) |
| cell discharge floor | -20 | -4 | p127 | Cell manufacturer's absolute lowest discharge temperature |
| storage floor | -20 | -4 | p127 | Storage below this may permanently decay the pack |
| sun storage ceiling | 35 | 95 | p128 | Storing in direct sunlight above this is not recommended |
Light line (LS1 / XB / XE) — MY2026
26_LS1_OM_-_EU_-_English_-_8812142-AG.pdf · LS1
| Figure | °C | °F | PDF page | What it governs |
|---|---|---|---|---|
| operating low | -20 | -4 | p43 | Pack operating range, low end — BMS turns off the power controller below |
| operating high | 55 | 131 | p43 | Pack operating range, high end — BMS turns off the power controller above |
| charge ambient low | -10 | 14 | p44 | Charging environment, low end |
| charge ambient high | 50 | 122 | p44 | Charging environment, high end |
S / DS / SR / DSR — MY2015
OM-SDS-MY15-English.pdf · DS, S, SR
| Figure | °C | °F | PDF page | What it governs |
|---|---|---|---|---|
| operating low | -5 | 23 | p56 | Pack operating range, low end — BMS turns off the power controller below |
| operating high | 60 | 140 | p56 | Pack operating range, high end — BMS turns off the power controller above |
| charge low | 0 | 32 | p56 | Charging inhibited below |
| charge high | 55 | 131 | p120 | Charging inhibited above |
| charge taper | 43 | 110 | p120 | Charge current begins to taper above |
| discharge high cutoff | 60 | 140 | p120 | Discharge (riding) blocked above |
| ride advisory low | -5 | 23 | p119 | Riding not recommended below (advisory, not a BMS cutoff) |
| cell discharge floor | -30 | -22 | p119 | Cell manufacturer's absolute lowest discharge temperature |
| storage floor | -35 | -31 | p119 | Storage below this may permanently decay the pack |
| sun storage ceiling | 41 | 105 | p120 | Storing in direct sunlight above this is not recommended |
S / DS / SR / DSR — MY2016
OM-SDS-MY16-English-06.pdf · DS, DSR, S, SR
| Figure | °C | °F | PDF page | What it governs |
|---|---|---|---|---|
| operating low | -5 | 23 | p63 | Pack operating range, low end — BMS turns off the power controller below |
| operating high | 60 | 140 | p63 | Pack operating range, high end — BMS turns off the power controller above |
| charge low | 0 | 32 | p63 | Charging inhibited below |
| charge high | 50 | 122 | p114 | Charging inhibited above |
| charge taper | 43 | 110 | p114 | Charge current begins to taper above |
| discharge high cutoff | 60 | 140 | p114 | Discharge (riding) blocked above |
| ride advisory low | -5 | 23 | p113 | Riding not recommended below (advisory, not a BMS cutoff) |
| cell discharge floor | -30 | -22 | p113 | Cell manufacturer's absolute lowest discharge temperature |
| storage floor | -35 | -31 | p113 | Storage below this may permanently decay the pack |
| sun storage ceiling | 41 | 105 | p114 | Storing in direct sunlight above this is not recommended |
S / DS / SR / DSR — MY2017
OM-SDS-MY17-English-AH.pdf · DS, DSR, S, SR
| Figure | °C | °F | PDF page | What it governs |
|---|---|---|---|---|
| operating low | -5 | 23 | p63 | Pack operating range, low end — BMS turns off the power controller below |
| operating high | 60 | 140 | p63 | Pack operating range, high end — BMS turns off the power controller above |
| charge low | 0 | 32 | p63 | Charging inhibited below |
| charge high | 50 | 122 | p120 | Charging inhibited above |
| charge taper | 43 | 110 | p120 | Charge current begins to taper above |
| discharge high cutoff | 60 | 140 | p120 | Discharge (riding) blocked above |
| ride advisory low | -5 | 23 | p119 | Riding not recommended below (advisory, not a BMS cutoff) |
| cell discharge floor | -30 | -22 | p119 | Cell manufacturer's absolute lowest discharge temperature |
| storage floor | -35 | -31 | p119 | Storage below this may permanently decay the pack |
| sun storage ceiling | 41 | 105 | p120 | Storing in direct sunlight above this is not recommended |
S / DS / SR / DSR — MY2018
OM-SDS-MY18-AF.pdf · DS, DSR, S, SR
| Figure | °C | °F | PDF page | What it governs |
|---|---|---|---|---|
| operating low | -5 | 23 | p65 | Pack operating range, low end — BMS turns off the power controller below |
| operating high | 60 | 140 | p65 | Pack operating range, high end — BMS turns off the power controller above |
| charge low | 0 | 32 | p65 | Charging inhibited below |
| charge high | 50 | 122 | p116 | Charging inhibited above |
| charge taper | 43 | 110 | p116 | Charge current begins to taper above |
| discharge high cutoff | 60 | 140 | p116 | Discharge (riding) blocked above |
| ride advisory low | -5 | 23 | p115 | Riding not recommended below (advisory, not a BMS cutoff) |
| cell discharge floor | -30 | -22 | p115 | Cell manufacturer's absolute lowest discharge temperature |
| storage floor | -35 | -31 | p115 | Storage below this may permanently decay the pack |
| sun storage ceiling | 41 | 105 | p116 | Storing in direct sunlight above this is not recommended |
S / DS / SR / DSR — MY2019
OM-SDS-MY19-04.pdf · DS, DSR, S, SR
| Figure | °C | °F | PDF page | What it governs |
|---|---|---|---|---|
| operating low | -20 | -4 | p65 | Pack operating range, low end — BMS turns off the power controller below |
| operating high | 60 | 140 | p65 | Pack operating range, high end — BMS turns off the power controller above |
| charge low | 0 | 32 | p65 | Charging inhibited below |
| charge high | 50 | 122 | p116 | Charging inhibited above |
| charge taper | 43 | 109 | p116 | Charge current begins to taper above |
| discharge high cutoff | 60 | 140 | p116 | Discharge (riding) blocked above |
| ride advisory low | -5 | 23 | p115 | Riding not recommended below (advisory, not a BMS cutoff) |
| cell discharge floor | -20 | -4 | p115 | Cell manufacturer's absolute lowest discharge temperature |
| storage floor | -20 | -4 | p115 | Storage below this may permanently decay the pack |
| sun storage ceiling | 35 | 95 | p116 | Storing in direct sunlight above this is not recommended |
S / DS / SR / DSR — MY2020
OM-SDS-MY20-English-03.pdf · DS, DSR, S, SR
| Figure | °C | °F | PDF page | What it governs |
|---|---|---|---|---|
| operating low | -20 | -4 | p65 | Pack operating range, low end — BMS turns off the power controller below |
| operating high | 60 | 140 | p65 | Pack operating range, high end — BMS turns off the power controller above |
| charge low | 0 | 32 | p65 | Charging inhibited below |
| charge high | 50 | 122 | p116 | Charging inhibited above |
| charge taper | 43 | 109 | p116 | Charge current begins to taper above |
| discharge high cutoff | 60 | 140 | p116 | Discharge (riding) blocked above |
| ride advisory low | -5 | 23 | p115 | Riding not recommended below (advisory, not a BMS cutoff) |
| cell discharge floor | -20 | -4 | p115 | Cell manufacturer's absolute lowest discharge temperature |
| storage floor | -20 | -4 | p115 | Storage below this may permanently decay the pack |
| sun storage ceiling | 35 | 95 | p116 | Storing in direct sunlight above this is not recommended |
S / DS / SR / DSR — MY2021
21MY_SDS_OM_-_English-04.pdf · DS, DSR, S, SR
| Figure | °C | °F | PDF page | What it governs |
|---|---|---|---|---|
| operating low | -20 | -4 | p63 | Pack operating range, low end — BMS turns off the power controller below |
| operating high | 60 | 140 | p63 | Pack operating range, high end — BMS turns off the power controller above |
| charge low | 0 | 32 | p63 | Charging inhibited below |
| charge high | 50 | 122 | p114 | Charging inhibited above |
| charge taper | 43 | 109 | p114 | Charge current begins to taper above |
| discharge high cutoff | 60 | 140 | p114 | Discharge (riding) blocked above |
| ride advisory low | -5 | 23 | p113 | Riding not recommended below (advisory, not a BMS cutoff) |
| cell discharge floor | -20 | -4 | p113 | Cell manufacturer's absolute lowest discharge temperature |
| storage floor | -20 | -4 | p113 | Storage below this may permanently decay the pack |
| sun storage ceiling | 35 | 95 | p114 | Storing in direct sunlight above this is not recommended |
S / DS / SR / DSR — MY2022
22MY_SDS_OM_-_English-04.pdf · DS, DSR, S
| Figure | °C | °F | PDF page | What it governs |
|---|---|---|---|---|
| operating low | -20 | -4 | p65 | Pack operating range, low end — BMS turns off the power controller below |
| operating high | 60 | 140 | p65 | Pack operating range, high end — BMS turns off the power controller above |
| charge low | 0 | 32 | p65 | Charging inhibited below |
| charge high | 50 | 122 | p116 | Charging inhibited above |
| charge taper | 43 | 109 | p116 | Charge current begins to taper above |
| discharge high cutoff | 60 | 140 | p116 | Discharge (riding) blocked above |
| ride advisory low | -5 | 23 | p115 | Riding not recommended below (advisory, not a BMS cutoff) |
| cell discharge floor | -20 | -4 | p115 | Cell manufacturer's absolute lowest discharge temperature |
| storage floor | -20 | -4 | p115 | Storage below this may permanently decay the pack |
| sun storage ceiling | 35 | 95 | p116 | Storing in direct sunlight above this is not recommended |
S / DS / SR / DSR — MY2023
23_SDS_OM_-_English-88-09956-06.pdf · DS, DSR, S
| Figure | °C | °F | PDF page | What it governs |
|---|---|---|---|---|
| operating low | -20 | -4 | p65 | Pack operating range, low end — BMS turns off the power controller below |
| operating high | 60 | 140 | p65 | Pack operating range, high end — BMS turns off the power controller above |
| charge low | 0 | 32 | p65 | Charging inhibited below |
| charge high | 50 | 122 | p116 | Charging inhibited above |
| charge taper | 43 | 109 | p116 | Charge current begins to taper above |
| discharge high cutoff | 60 | 140 | p116 | Discharge (riding) blocked above |
| ride advisory low | -5 | 23 | p115 | Riding not recommended below (advisory, not a BMS cutoff) |
| cell discharge floor | -20 | -4 | p115 | Cell manufacturer's absolute lowest discharge temperature |
| storage floor | -20 | -4 | p115 | Storage below this may permanently decay the pack |
| sun storage ceiling | 35 | 95 | p116 | Storing in direct sunlight above this is not recommended |
SR/F & SR/S — MY2020
OM-SRF-MY20.pdf · SR/F
| Figure | °C | °F | PDF page | What it governs |
|---|---|---|---|---|
| operating low | -20 | -4 | p97 | Pack operating range, low end — BMS turns off the power controller below |
| operating high | 60 | 140 | p97 | Pack operating range, high end — BMS turns off the power controller above |
| charge low | 0 | 32 | p97 | Charging inhibited below |
| charge high | 50 | 122 | p147 | Charging inhibited above |
| charge taper | 43 | 110 | p147 | Charge current begins to taper above |
| discharge high cutoff | 60 | 140 | p147 | Discharge (riding) blocked above |
| ride advisory low | -5 | 23 | p146 | Riding not recommended below (advisory, not a BMS cutoff) |
| cell discharge floor | -30 | -22 | p146 | Cell manufacturer's absolute lowest discharge temperature |
| storage floor | -35 | -31 | p146 | Storage below this may permanently decay the pack |
| sun storage ceiling | 41 | 105 | p147 | Storing in direct sunlight above this is not recommended |
| hv12 heater on | 5 | 41 | p146 | 12 V battery heater engages below (Cypher III only) |
SR/F & SR/S — MY2020
OM-SRS-MY20.pdf · SR/S
| Figure | °C | °F | PDF page | What it governs |
|---|---|---|---|---|
| operating low | -20 | -4 | p101 | Pack operating range, low end — BMS turns off the power controller below |
| operating high | 60 | 140 | p101 | Pack operating range, high end — BMS turns off the power controller above |
| charge low | 0 | 32 | p101 | Charging inhibited below |
| charge high | 50 | 122 | p154 | Charging inhibited above |
| charge taper | 43 | 110 | p154 | Charge current begins to taper above |
| discharge high cutoff | 60 | 140 | p154 | Discharge (riding) blocked above |
| ride advisory low | -5 | 23 | p153 | Riding not recommended below (advisory, not a BMS cutoff) |
| cell discharge floor | -30 | -22 | p153 | Cell manufacturer's absolute lowest discharge temperature |
| storage floor | -35 | -31 | p153 | Storage below this may permanently decay the pack |
| sun storage ceiling | 41 | 105 | p154 | Storing in direct sunlight above this is not recommended |
| hv12 heater on | 5 | 41 | p153 | 12 V battery heater engages below (Cypher III only) |
SR/F & SR/S — MY2021
21MY_SRF_OM_-_English-05.pdf · SR/F
| Figure | °C | °F | PDF page | What it governs |
|---|---|---|---|---|
| operating low | -20 | -4 | p101 | Pack operating range, low end — BMS turns off the power controller below |
| operating high | 60 | 140 | p101 | Pack operating range, high end — BMS turns off the power controller above |
| charge low | 0 | 32 | p101 | Charging inhibited below |
| charge high | 50 | 122 | p156 | Charging inhibited above |
| charge taper | 43 | 110 | p156 | Charge current begins to taper above |
| discharge high cutoff | 60 | 140 | p156 | Discharge (riding) blocked above |
| ride advisory low | -5 | 23 | p155 | Riding not recommended below (advisory, not a BMS cutoff) |
| cell discharge floor | -30 | -22 | p155 | Cell manufacturer's absolute lowest discharge temperature |
| storage floor | -35 | -31 | p155 | Storage below this may permanently decay the pack |
| sun storage ceiling | 41 | 105 | p156 | Storing in direct sunlight above this is not recommended |
| hv12 heater on | 5 | 41 | p155 | 12 V battery heater engages below (Cypher III only) |
SR/F & SR/S — MY2021
OM-SRS-MY21-English-05.pdf · SR/S
| Figure | °C | °F | PDF page | What it governs |
|---|---|---|---|---|
| operating low | -20 | -4 | p101 | Pack operating range, low end — BMS turns off the power controller below |
| operating high | 60 | 140 | p101 | Pack operating range, high end — BMS turns off the power controller above |
| charge low | 0 | 32 | p101 | Charging inhibited below |
| charge high | 50 | 122 | p156 | Charging inhibited above |
| charge taper | 43 | 110 | p156 | Charge current begins to taper above |
| discharge high cutoff | 60 | 140 | p156 | Discharge (riding) blocked above |
| ride advisory low | -5 | 23 | p155 | Riding not recommended below (advisory, not a BMS cutoff) |
| cell discharge floor | -30 | -22 | p155 | Cell manufacturer's absolute lowest discharge temperature |
| storage floor | -35 | -31 | p155 | Storage below this may permanently decay the pack |
| sun storage ceiling | 41 | 105 | p156 | Storing in direct sunlight above this is not recommended |
| hv12 heater on | 5 | 41 | p155 | 12 V battery heater engages below (Cypher III only) |
SR/F & SR/S — MY2022
22MY_FST_OM_-_English-06.pdf · SR, SR/F, SR/S
| Figure | °C | °F | PDF page | What it governs |
|---|---|---|---|---|
| operating low | -20 | -4 | p87 | Pack operating range, low end — BMS turns off the power controller below |
| operating high | 60 | 140 | p87 | Pack operating range, high end — BMS turns off the power controller above |
| charge low | 0 | 32 | p87 | Charging inhibited below |
| charge high | 50 | 122 | p151 | Charging inhibited above |
| charge taper | 43 | 110 | p151 | Charge current begins to taper above |
| discharge high cutoff | 60 | 140 | p151 | Discharge (riding) blocked above |
| ride advisory low | -5 | 23 | p150 | Riding not recommended below (advisory, not a BMS cutoff) |
| cell discharge floor | -30 | -22 | p150 | Cell manufacturer's absolute lowest discharge temperature |
| storage floor | -35 | -31 | p150 | Storage below this may permanently decay the pack |
| sun storage ceiling | 41 | 105 | p151 | Storing in direct sunlight above this is not recommended |
| hv12 heater on | 5 | 41 | p150 | 12 V battery heater engages below (Cypher III only) |
SR/F & SR/S — MY2023
23_FST_Street_OM_-_English_-_88-09961-AK.pdf · SR, SR/F, SR/S
| Figure | °C | °F | PDF page | What it governs |
|---|---|---|---|---|
| operating low | -20 | -4 | p87 | Pack operating range, low end — BMS turns off the power controller below |
| operating high | 60 | 140 | p87 | Pack operating range, high end — BMS turns off the power controller above |
| charge low | 0 | 32 | p87 | Charging inhibited below |
| charge high | 50 | 122 | p151 | Charging inhibited above |
| charge taper | 43 | 110 | p151 | Charge current begins to taper above |
| discharge high cutoff | 60 | 140 | p151 | Discharge (riding) blocked above |
| ride advisory low | -5 | 23 | p150 | Riding not recommended below (advisory, not a BMS cutoff) |
| cell discharge floor | -30 | -22 | p150 | Cell manufacturer's absolute lowest discharge temperature |
| storage floor | -35 | -31 | p150 | Storage below this may permanently decay the pack |
| sun storage ceiling | 41 | 105 | p151 | Storing in direct sunlight above this is not recommended |
| hv12 heater on | 5 | 41 | p150 | 12 V battery heater engages below (Cypher III only) |
SR/F & SR/S — MY2024
24_FST_Street_OM_-_English_-_EU_-_8811911-AI.pdf · S, SR, SR/F, SR/S
| Figure | °C | °F | PDF page | What it governs |
|---|---|---|---|---|
| operating low | -20 | -4 | p87 | Pack operating range, low end — BMS turns off the power controller below |
| operating high | 60 | 140 | p87 | Pack operating range, high end — BMS turns off the power controller above |
| charge low | 0 | 32 | p87 | Charging inhibited below |
| charge high | 50 | 122 | p151 | Charging inhibited above |
| charge taper | 43 | 110 | p151 | Charge current begins to taper above |
| discharge high cutoff | 60 | 140 | p151 | Discharge (riding) blocked above |
| ride advisory low | -5 | 23 | p150 | Riding not recommended below (advisory, not a BMS cutoff) |
| cell discharge floor | -30 | -22 | p150 | Cell manufacturer's absolute lowest discharge temperature |
| storage floor | -35 | -31 | p150 | Storage below this may permanently decay the pack |
| sun storage ceiling | 41 | 105 | p151 | Storing in direct sunlight above this is not recommended |
| hv12 heater on | 5 | 41 | p150 | 12 V battery heater engages below (Cypher III only) |
SR/F & SR/S — MY2025
25_FST_Street_EU_-_English-_8811978-AG.pdf · S, SR, SR/F, SR/S
| Figure | °C | °F | PDF page | What it governs |
|---|---|---|---|---|
| operating low | -20 | -4 | p87 | Pack operating range, low end — BMS turns off the power controller below |
| operating high | 60 | 140 | p87 | Pack operating range, high end — BMS turns off the power controller above |
| charge low | 0 | 32 | p87 | Charging inhibited below |
| charge high | 50 | 122 | p151 | Charging inhibited above |
| charge taper | 43 | 110 | p151 | Charge current begins to taper above |
| discharge high cutoff | 60 | 140 | p151 | Discharge (riding) blocked above |
| ride advisory low | -5 | 23 | p150 | Riding not recommended below (advisory, not a BMS cutoff) |
| cell discharge floor | -30 | -22 | p150 | Cell manufacturer's absolute lowest discharge temperature |
| storage floor | -35 | -31 | p150 | Storage below this may permanently decay the pack |
| sun storage ceiling | 41 | 105 | p151 | Storing in direct sunlight above this is not recommended |
| hv12 heater on | 5 | 41 | p150 | 12 V battery heater engages below (Cypher III only) |
SR/F & SR/S — MY2026
26_FST_Street-_EU_-_English-_8812119-AC.pdf · S, SR/F
| Figure | °C | °F | PDF page | What it governs |
|---|---|---|---|---|
| operating low | -20 | -4 | p87 | Pack operating range, low end — BMS turns off the power controller below |
| operating high | 60 | 140 | p87 | Pack operating range, high end — BMS turns off the power controller above |
| charge low | 0 | 32 | p87 | Charging inhibited below |
| charge high | 50 | 122 | p151 | Charging inhibited above |
| charge taper | 43 | 110 | p151 | Charge current begins to taper above |
| discharge high cutoff | 60 | 140 | p151 | Discharge (riding) blocked above |
| ride advisory low | -5 | 23 | p150 | Riding not recommended below (advisory, not a BMS cutoff) |
| cell discharge floor | -30 | -22 | p150 | Cell manufacturer's absolute lowest discharge temperature |
| storage floor | -35 | -31 | p150 | Storage below this may permanently decay the pack |
| sun storage ceiling | 41 | 105 | p151 | Storing in direct sunlight above this is not recommended |
| hv12 heater on | 5 | 41 | p150 | 12 V battery heater engages below (Cypher III only) |
Frequently asked questions
How cold can you ride a Zero?
It depends on the model year, and there are two answers because Zero gives two figures. The BMS turns off the power controller below -5 °C (23 °F) on a MY2016–2018 S, DS, SR, DSR, FX or FXS and below -20 °C (-4 °F) from MY2019 onward, including every SR/F, SR/S, DSR/X and ADV. Separately, every manual advises against riding below -5 °C (23 °F). The -30 °C figure widely quoted is a cell-chemistry floor from the storage chapter and is not where the bike stops.
Why will my Zero not charge in the cold?
Because the BMS refuses to charge below 0 °C (32 °F) on every motorcycle platform in the index: 34 of the 35 documents state a pack charge floor and all 34 give that same figure. (The one that does not is the LS1 scooter manual, which states a charging-environment range instead.) The manuals also give the practical consequence: if you ride the bike cold, put it on the charger somewhere above 0 °C (32 °F) as soon as the ride ends, rather than leaving it cold and discharged.
At what temperature does a Zero stop charging in the heat?
Above 50 °C (122 °F) on everything from MY2016 onward, and above 55 °C (131 °F) on MY2015 bikes. Before that hard stop, charge current tapers from 43 °C (109 °F) upward, so a slow charge on a hot day is normal behaviour rather than a fault. Riding, by contrast, continues to 60 °C (140 °F).
What does the temperature warning light on my Zero mean?
On a Gen2 bike the yellow lamp has two stages in Zero’s own words: flashing means the bike is about to enter its thermal strategy and performance is not yet affected, solid means power is being reduced. On a Cypher III bike there is one red lamp, solid, and by the time it is on power is already reduced — the gauges are the early warning instead. Zero publishes no temperature at which either lamp lights.
What is the maximum motor temperature on a Zero?
Zero publishes one figure and it applies only to the Cypher III bikes: the dash motor gauge turns red at 118 °C (244 °F) and its scale ends at 150 °C (302 °F), in 13 manuals. For Gen2 bikes there is no published figure at all; the 100 C and 145 C numbers in circulation were read off one 2016 SR over its CAN bus and may not describe your firmware.
Does cold weather permanently damage a Zero battery?
Riding in it, no — the manuals state that cold weather operation "has no permanent impact on its power pack/cells" and that the range loss is temporary. Storing it cold, yes: below the storage floor for your model year (-35 °C (-31 °F) through MY2018 on the Gen2 platforms, -20 °C (-4 °F) from MY2019, -35 °C (-31 °F) on the Cypher III bikes) Zero warns of "accelerated permanent decay". Keep the pack above 30% state of charge through the winter.
Where do these numbers come from?
They are extracted from 35 of Zero’s own manuals by `backend/scripts/gen_thermal_limits.py`, which reads the indexed text of the manual PDFs, anchors on Zero’s phrasing rather than on any number, checks every Fahrenheit/Celsius pair against the definition of the unit, and emits a generated TypeScript module. Nothing on this page is typed by hand: the prose interpolates the same data the tables and the figure render. The page numbers are not taken from the text index either: each is looked for in the PDF with `pdftotext`, because a block of indexed text spans four or five pages and citing where the block starts put a quarter of these citations one page out. 360 of 360 are confirmed that way.
Every temperature on this page was read out of Zero’s own manuals: 35 documents covering model years 2015 to 2026, indexed as text and parsed by `backend/scripts/gen_thermal_limits.py`, which emits `thermal-data.generated.ts` alongside this article. Reproduce it with `python3 backend/scripts/gen_thermal_limits.py --report`; CI fails on a stale generated file via `--check`. The manual PDFs are Zero’s, published for download, and page references are PDF pages in the file named — each one looked for in the PDF itself with `pdftotext` rather than read off the indexed text block, a distinction that matters because citing where the block began put 90 of these 360 citations exactly one page out while every temperature on them was correct. 360 of 360 are confirmed in the PDF, and nothing is published as traceable without being found there. The community archive is cited only where this page documents an error in it, and is linked to the Internet Archive because zeromanual.com stopped responding in March 2026. Where the archive and a manual disagreed, the manual won, and the disagreement is left in place with the measurement that settled it rather than being silently dropped. Two of our own earlier claims are retracted on this page for the same reason. Last extracted 2026-08-08.
Sources:
This is an independent third-party reference, not affiliated with or endorsed by Zero Motorcycles, Inc. It reproduces temperature figures from Zero’s published manuals for reference; your own model-year manual is the authority, and a figure here that disagrees with it is wrong. Nothing here is a substitute for a qualified technician, and nothing here authorises work on the high-voltage system.